DPMS XPQ User Manual
The voltage and current input wiring mode can be set separately in the meter
parameter setting process. The voltage wiring mode could be 3-phase 4-line
Wye (3LN), 3-phase 4-line 2PT Wye mode (2LN) and 3-phase 3-line open delta
(2LL). The current input wiring mode could be 3CT, 2CT and 1CT. Any voltage
mode could be grouped with one of the current modes.
Voltage Input Wiring
3-Phase 4-Line Wye mode (3LN)
The 3-Phase 4-Line Wye mode is commonly used in low voltage electric
distribution power systems. The power line can be connected to the meter
voltage input directly as in g 2.10a. In the high voltage input system, 3PT Wye
mode is often used as in g 2.10b. The voltage input mode of the DPMS XPQ
should be set to 3LN for both voltage input wiring modes.
Fig 2.10a 3LN direct connection
Acuvim-X