18
DPMS XPQ User Manual
Fig 2.8 Wiring of Power Supply
A fuse (typical 1A/250Vac) should be used in the auxiliary power supply
loop. No.24 terminal must be connected to the safety earth system of
switchgear. An isolated transformer or EMI lter should be used in the auxiliary
power supply loop if there is a power quality problem in the power supply.
Fig 2.9 Wiring of Aux. Power Supply with power line lter
Choice of wire should be AWG22~16 or 0.6~1.3mm
2
.
Note: A lter should be used if there is an EMI problem.
Voltage Input
Meter input voltage should be 40~230Vac L-N,
60~400Vac. L-L. The voltage input could be directly
connected to the meter terminal without the use of PT if
the voltage system is less than 400Vac (L-L). If the input
Voltage is higher than 400Vac, a PT or VT should be
Note
The secondary of PT
c a n n o t be s h o r t e d ,
otherwise it may cause
the severe damage of
the instrument.
Note
Mak e s ure the powe r
supply voltage is the
same as what the meter
needs for its auxiliary
power.
L
N Acuvim-X
G
20
22
24
Power Supply
1A FUSE
Ground
L
N Acuvim-X
G
20
22
24
L L
N N
G G
Power Supply
1A FUSE
Ground
Power
lter