DPMS XPQ User Manual
Fig 2.8 Wiring of Power Supply
A fuse (typical 1A/250Vac) should be used in the auxiliary power supply
loop. No.24 terminal must be connected to the safety earth system of
switchgear. An isolated transformer or EMI lter should be used in the auxiliary
power supply loop if there is a power quality problem in the power supply.
Fig 2.9 Wiring of Aux. Power Supply with power line lter
Choice of wire should be AWG22~16 or 0.6~1.3mm
2
.
Note: A lter should be used if there is an EMI problem.
Voltage Input
Meter input voltage should be 40~230Vac L-N,
60~400Vac. L-L. The voltage input could be directly
connected to the meter terminal without the use of PT if
the voltage system is less than 400Vac (L-L). If the input
Voltage is higher than 400Vac, a PT or VT should be
Note
The secondary of PT
c a n n o t be s h o r t e d ,
otherwise it may cause
the severe damage of
the instrument.
Note
Mak e s ure the powe r
supply voltage is the
same as what the meter
needs for its auxiliary
power.
L
N Acuvim-X
G
20
22
24
Power Supply
1A FUSE
Ground
L
N Acuvim-X
G
20
22
24
L L
N N
G G
Power Supply
1A FUSE
Ground
Power
lter