POWER INSTRUMENTSDPMS XPQ Multi-Function Power MeterUser Manual 1087-332

Seite 2

8DPMS XPQ User ManualApplication AreaPower Distribution Automation Intelligent Electric Switch GearIndustry Automation Building AutomationEnergy Manag

Seite 3

98DPMS XPQ User ManualResponseThe normal response to a preset Multi-Register request includes the meter's address, function code, data s

Seite 4

99POWER INSTRUMENTSparameters relationship unit Format codeSystem parameters Numerical value equals to communication valueNo unit F1Run time T=Rx/100

Seite 5

100DPMS XPQ User ManualSystem Parameter SettingSystem parameters determine how the meter works. You should understand it clearly by referring

Seite 6

101POWER INSTRUMENTS1011H Relay2 Pulse Width 200 50~30001012H LCD Back light Time 1 0~1201013H Demand Slid Window Time 15 1~601014H Max/Min

Seite 7 - Chapter 1 Introduction

102DPMS XPQ User Manual1028H TOU enable 1 Only1 works1029H TOU default enable 1 Only 1 works102AH Real time energy clearance 1 Only 1 works1

Seite 8

103POWER INSTRUMENTS103FH Apparent power measuringmode1 0,11040H DI triggering demandsynchronization enable0 0~41041H DI triggering condition 1 1~

Seite 9 - Metering Energy

104DPMS XPQ User ManualRead-only Record Pointer and its Status“Pointer” is the index number of the addresses of coming-up records.” 0”stands fo

Seite 10 - DPMS XPQ User Manual

105POWER INSTRUMENTSDate and Time TableFunction code: 03 for Reading, 16 for Presetting.Address Parameter Range Format code1080H Year 2000~2099 F

Seite 11

106DPMS XPQ User Manual1087H~108BH Start time of rst schedule: mm:dd:hh:mm:ssTime F3108CH~1090H End time of rst schedule: mm:dd:hh:mm:ssTime F31

Seite 12

107POWER INSTRUMENTS11B4H~11C3H In series, they are generation energy, inductive energy, capacitive energy, absolute sum of imp and exp energy, alge

Seite 13 - Chapter 2 Installation

9POWER INSTRUMENTSEEprom, which will maintain its content after the meter is powered off. With the backlight of the LCD, the display can be easily rea

Seite 14 - Appearance and Dimensions

108DPMS XPQ User Manualenergy(valley), Phase B inductive energy(valley), Phase B consumption energy(normal), Phase B generation energy(normal), Phase

Seite 15 - Fig 2.2 Dimensions

109POWER INSTRUMENTSTOU of Current MonthTOU of current month is stored here. It refreshes every second and clears at the balance time. Function code:

Seite 16

110DPMS XPQ User ManualAlarming RecordsThere are 16 groups of records with the same format. Function code: 03H for Reading, 10H for writing. Please re

Seite 17

111POWER INSTRUMENTSFunction code: 03H for Reading, 10H for writing. Please refer to chapter 4 for more details.Address Parameter Range Data type16

Seite 18

112DPMS XPQ User ManualVoltage EligibilityFunction code: 03H for Reading, 10H for writing, data type: word.Address Parameter Range Format code32A8H

Seite 19 - Note

113POWER INSTRUMENTS32D6H,32D7H Day: eligible time of three phase 0.0~3.402823E +38 F2432D8H~32E1H month: same as day 0.0~3.402823E +38 F2432E2H

Seite 20

114DPMS XPQ User Manual3372H~337BH Year: same as day 0.0~3.402823E +38 F24The following are statistics of Voltage Eligibility337CH,337DH Day: elig

Seite 21

115POWER INSTRUMENTSAddress Parameter Relationship Unit4000H,4001H Frequency F=Rx / 100 Hz4002H,4003H Phase voltage V1 U=Rx X (PT1 / PT2) V4004

Seite 22 - Acuvim-X

116DPMS XPQ User Manual402cH,402dH Phase A Apparent power Sa S=Rx X (PT1 / PT2) X (CT1/5)VA402eH,402fH Phase B Apparent power SbS=Rx X (PT1 / PT2) X

Seite 23

117POWER INSTRUMENTS4043H THD_V1 of V2(V23) 0~10000 F154044H THD_V1 of V3(V31) 0~10000 F154045H THD_V 0~10000 F154046H THD_I1 0~10000 F154047H TH

Seite 24

10DPMS XPQ User ManualHarmonics THD Phases and all ● ● ●phase ● ●Voltage harmonic analysis ● ●current harmonic analysis ● ●FunctionD E F GSequence ●

Seite 25 - Current Input Wiring

118DPMS XPQ User Manual4124H Last positive power demand of phase A 0~32767 F34125H Current positive power demand of phase A 0~32767 F34126H P e

Seite 26

119POWER INSTRUMENTS41a2H~41aaH Inductive power demand of three phase(like positive power demand of A phase )F1041abH~41b3H capacitive power dem

Seite 27 - 1. 3LN, 3CT with 3 CTs

120DPMS XPQ User ManualMAX/MIN recordMAX/MIN and related time. Function code: 03H for Reading.Address Parameter Range Format code41e6H MAX of V1 0~

Seite 28 - 3. 2LN, 2CT

121POWER INSTRUMENTS4241H MAX of frequency 0~7000 F134242H~4247H Occur time: yyyy:mm:dd:hh:mm:ss time F34248H MAX of power demand -32768~3276

Seite 29 - Fig 2.21 2LN, 1CT

122DPMS XPQ User ManualSequence ComponentU1 (U12), I1 consist of real and complex parts. They have positive sequence, negative sequence and

Seite 30 - 7. 2LL, 1CT

123POWER INSTRUMENTS44b8H phase angle of I3 to V1 0~3600 F2244b9H phase angle of V23 to V12 0~3600 F2244baH phase angle of I1 to V12 0~3600 F22

Seite 32 - Isolator

125AppendixAppendix A Technical Data and SpecicationsAppendix B Ordering Information

Seite 33

126DPMS XPQ User ManualAppendix A Technical data and specicationsInput RatingsVoltage Input Voltage rating

Seite 34 - Photo -Mos

127POWER INSTRUMENTSAccuracyParameter AccuracyVoltage10.2%Current2 0.2%Power 0.5%Reactive Power 0.5%Apparent Power 0.5%Power Factor 0.5%Frequency

Seite 35 - g 2.31 Do Alarming Circult

Chapter 2 InstallationAppearance and DimensionsInstallation MethodWiring11

Seite 36 - Acuvim-X Acuvim-X Acuvim -X

128DPMS XPQ User ManualDigital Input (DI)Optical Isolation Isolate voltage 2500Vac rmsInput Type Wet contact (Contact with power supply)Input resis

Seite 37 - g 2.31 Star Mode

129POWER INSTRUMENTS Suitable ConditionsDimensions (mm) 96x96x72 (Cut -out90x90)Protection Level IP52 (Front) IP20 ( Cover)Weight (g) 350Temperatur

Seite 38

130DPMS XPQ User ManualAppendix B ORDERING INFORMATIONDPMS XPQ D-------DPMS XPQ-DE-------DPMS XPQ-EF-------DPMS XPQ-FG------DPMS XPQ-GD: Base unit wit

Seite 40

AMETEK Power Instruments255 North Union Street, Rochester NY, 14605 U.S.A.585-263-7700 Tel. 585-454-7805 [email protected]

Seite 41

12DPMS XPQ User ManualNote: Before trying to operate the meter, note the functions according to its pattern. The installation method is introdu

Seite 42

13POWER INSTRUMENTSDimensionsFig 2.2 DimensionsInstallation MethodEnvironmentalBefore installation, please check the environment temperature and humid

Seite 43

14DPMS XPQ User ManualThe meter should be installed in a dry and dust free environment and avoid heat, radiation and high electrical noise sources.Max

Seite 44

15POWER INSTRUMENTS3. Finally, install clips back on the meter from the backside and push the clip tightly so that the meter is afxed on the panel.

Seite 45

16DPMS XPQ User ManualEnvironment Temperature Minimum Distance(mm) a b c d e f g<50< 25 25 38 38 64 25 25 ≥50< 38 38 51 51 76 38 38Table 2.2 Min

Seite 46

17POWER INSTRUMENTSExtend Terminal StripFig 2.7 Terminal StripsSafety Earth ConnectionBefore doing the meter wiring connection, please make sure th

Seite 48

18DPMS XPQ User Manual Fig 2.8 Wiring of Power SupplyA fuse (typical 1A/250Vac) should be used

Seite 49

19POWER INSTRUMENTSused. A fuse (typical 1A/250Vac) should be used in the voltage input loop. A PT should be used to transform the high voltage into t

Seite 50

20DPMS XPQ User ManualThe voltage and current input wiring mode can be set separately in the meter parameter setting process. The voltage wiring mod

Seite 51

21POWER INSTRUMENTSFig 2.10b 3LN with 3PT3-Phase 3-Line direct connection mode (3LN)In a 3-Phase 3-Line system, power line A, B and C are connected to

Seite 52

22DPMS XPQ User Manual3-Phase 4-Line 2PT mode (2LN)In some 3-Phase 4-Line Wye systems, 2PT Wye mode is often used as in g 2.12. It is supposed that t

Seite 53

23POWER INSTRUMENTSCurrent Input Wiring3CTAll current input of a three phase system can be viewed as 3CT, whether there are 2 CTs or 3 CTs on the in

Seite 54

24DPMS XPQ User Manual2CTThe difference in g. 2.16 and g. 2.15 is that there is not current input in the I21 and I22 terminals. The I2 value is

Seite 55

25POWER INSTRUMENTSFrequently used wiring methodThe voltage and current wiring method are put together in one drawing. The DPMS XPQ meter will disp

Seite 56

26DPMS XPQ User Manual2. 3LN, 3CT with 2 CTsFig 2.19 3LN, 3CT with 2 CTs3. 2LN, 2CTFig 2.20 2LN, 2CT

Seite 57

27POWER INSTRUMENTS4. 2LN, 1CTFig 2.21 2LN, 1CT5. 2LL, 3CTFig 2.22 2LN, 3CTAcuvim-XFig 2.21 2LN, 1CT

Seite 58

IPOWER INSTRUMENTSCopyright 2008© V1.0This manual may not be reproduced in whole or in part by any means, without the expressed written consent

Seite 59

28DPMS XPQ User Manual6. 2LL, 2CTFig 2.23 2LL, 2CT7. 2LL, 1CTFig 2.24 2LL, 1CT

Seite 60

29POWER INSTRUMENTS8. Single Phase 2 Line (Wiring mode setting 3LN, 3CT)Fig 2.25 Single Phase 2 Lines9. Single Phase 3 Line (Wiring mode setting 3LN,

Seite 61

30DPMS XPQ User ManualWiring of Digital InputsThere are two digital inputs of wet contact in the standard DPMS XPQ. The terminals of the two digital

Seite 62

31POWER INSTRUMENTSFig 2.28 Digital Input with Auxiliary PowerRelay Output (RO)There are two additional relay output options for the DPMS XPQ

Seite 63 - Fig 4.4 Phase Angles

32DPMS XPQ User ManualThere are two mode selections for relay output, one is latching, and the other is momentary. For the latching mode, the rel

Seite 64

33POWER INSTRUMENTSprogrammed as energy pulse output. For example, DO1 is used as energy pulse output and DO2 is used as reactive energy puls

Seite 65 - Fig 4.6 Max and Min

34DPMS XPQ User Manualoverall length of the RS485 cable connecting all devices can not exceed 1200m (4000ft). The DPMS XPQ is used as a slave device o

Seite 66

35POWER INSTRUMENTSg 2.31 Circle Mode3. StarThe connection for RS485 net is in Wye mode. An anti-signal reflecting resistor may be needed in e

Seite 67

36DPMS XPQ User ManualRecommendations for high quality communication: Good quality shielded twisted pair of AWG22 (0.6mm2) or larger is very importan

Seite 68 - Here is to set demand:

Chapter 3 Meter Operation and Parameter SettingDisplay Panel and KeysMetering Data ReadingStatistics DisplayMeter Parameter SettingEnergy Parameter Se

Seite 69 - Fig 4.8 Demand Setting

IIDPMS XPQ User ManualPlease read this manual carefully before installation, operation and maintenance of the DPMS XPQ meter.The following s

Seite 70

38DPMS XPQ User ManualDetailed human-machine interface of the meter will be described in this chapter. It includes how to get the metering data a

Seite 71 - Fig 4.10 Current Month TOU

39POWER INSTRUMENTSTable 3.1 Display Panel descriptionSN Display Description1Four lines of letter in themetering areaDisplay metering data: Vol

Seite 72

40DPMS XPQ User ManualThere are four keys on the front panel, labeled as H, P, E and V/A from left to right. Use these four keys to read metering data

Seite 73 - Fig 4.12 Cumulative TOU

41POWER INSTRUMENTSPress P, to display power related data. The screen will scroll to the next display as you press P each time. It will go ba

Seite 74

42DPMS XPQ User ManualPress H, to display power quality data, including THD, unbalance factor and voltage eligibility. The screen will scrol

Seite 75

43POWER INSTRUMENTSTotal ener gyNet ener gyThe absor pti on reactive ener gyConsum pti on energyGener ation ener gyEEEEEThe gener ation reactive ener

Seite 76

44DPMS XPQ User ManualStatistics DisplayPress the P and V/A keys simultaneously, the Max and Min value of metering data will be displayed

Seite 77

45POWER INSTRUMENTSMeter Parameter SettingUnder the metering data display mode, press the H and V/A key simultaneously, to get into the m

Seite 78

46DPMS XPQ User Manual01: It is any digit from 1 - 247.02: 1200, 2400, 4800, 9600, 19200, 38400bps are available.03: Voltage input could

Seite 79

47POWER INSTRUMENTSreactive energy and generation of reactive energy respectively.10: The same as DO1 for setting, and they don’t affect each ot

Seite 80

IIIPOWER INSTRUMENTScontentChapter 1 Introduction……………………………………………………………………………6Purpose...………………………………………………………7Applicat

Seite 81

48DPMS XPQ User Manualpress any key if it is “off”.18: 0 and 1 stands for current month and current day respectively.19: To clear the Max and Mi

Seite 82

49POWER INSTRUMENTSON to OFF; “3” stands for trigger at any change.27, 28, and 29: To adjust polarity of the current, the threecurrents direction can

Seite 83

50DPMS XPQ User Manualoutput to DO2. On the panel, it is set as decimal but in the register it is binary, so it needs conversion.36, 37: The same

Seite 84

51POWER INSTRUMENTS44: This is the last screen of the setting page. The access code can be changed on this page. It is important to remember

Seite 85 - Fig 4.17 SOE Log

52DPMS XPQ User ManualEnergy Parameter setting Pressing H and E simultaneously under the metering data display mode will enter the energy set

Seite 86

53POWER INSTRUMENTS07: This screen will display only when you select the “at once”. 08: Set your time of freezing on this screen when you sel

Seite 87 - Fig 4.18 Waveform Log

54DPMS XPQ User ManualVoltage Eligibility Parameter SettingPressing H and P simultaneously under the metering data display mode will enter the voltag

Seite 88

55POWER INSTRUMENTS03, 04: when the meter is set to “2LL”, it is U23 andU2 for others.05, 06: when the meter is set to “2LL”, it is U31 andU3 for othe

Seite 89

56DPMS XPQ User Manual09, 10: Set the time for the “assign” mode.11: It only freezes real time measurement. There are two modes. “Assign” means poi

Seite 90

Chapter 4 Function and SoftwareFunctionality and Utility Software57

Seite 91 - Chapter 5 Communication

IVDPMS XPQ User ManualGetting Started!Congratulations!You have received an advanced, versatile, multifunction power meter, also known as a Remote te

Seite 92

58DPMS XPQ User ManualThe DPMS XPQ can measure almost all the parameters in the power system. Some of its functions may not be demonstrated

Seite 93 - Table5.2 Function Code

59POWER INSTRUMENTSNote1: It should be clear that there is a dened correspondence between the real value and communication value. For more detail,

Seite 94

60DPMS XPQ User ManualA chart in the software is shown below:Fig 4.3 Voltage SpectrumPhase anglePhase angle indicates the angle between U1 and other v

Seite 95

61POWER INSTRUMENTSFig 4.4 Phase AnglesCurrent direction adjustmentThe right current direction is from port 1 to port 2. To adjust polarity

Seite 96

62DPMS XPQ User ManualFig 4.5 Sequence ComponentMax/MinThe meter can record statistics of the maximum and minimum values of phase/line voltages,

Seite 97

63POWER INSTRUMENTSThe following gure is an example:Fig 4.6 Max and MinDemandTypes of demands calculated are: consumption power demand of phases A,

Seite 98

64DPMS XPQ User Manualpower demand, current demand of I1, current demand of I2, current demand of I3, current demand of average current, consumption p

Seite 99

65POWER INSTRUMENTScalculation and the demands update at the end of each period.Synchronization demandWhen it is set as a xed window, rolling wind

Seite 100

66DPMS XPQ User ManualHere is an example:Fig 4.7 DemandHere is to set demand:

Seite 101 - POWER INSTRUMENTS

67POWER INSTRUMENTSFig 4.8 Demand SettingEnergyVarious kinds of energy will be accumulated. The settings are explained in other chapters, so please re

Seite 102 - Format code: F1

Chapter 1 IntroductionPurposeApplication AreaFunctionsDPMS XPQ Series5

Seite 103

68DPMS XPQ User ManualFig 4.9 Real-Time EnergyTOUYou can point some different time block to go with different rates (sharp, peak, valley and no

Seite 104

69POWER INSTRUMENTSThe following is an example:Fig 4.10 Current Month TOUCalculating mode1. You can select calculating mode from a fundamental base

Seite 105

70DPMS XPQ User ManualMode 1: The following gure shows how to set it:Fig 4.11 Energy SettingFreezingThis is to backup the accumulated TOU, current TO

Seite 106

71POWER INSTRUMENTSFig 4.12 Cumulative TOUTOU calendar:There are four schedules and each schedule has 8 time intervals. Each interval can charge

Seite 107

72DPMS XPQ User ManualYou can adjust the calendar to satisfy different uses. To ensure the validity of the calendar setting, the meter will check it

Seite 108 - Real Time Energy Measurement

73POWER INSTRUMENTSFig 4.13 TOU Schedules SettingPulse Energy OutputThe two digital outputs can be used as energy pulse output and cannot be used

Seite 109 - Energy Freezing

74DPMS XPQ User ManualPulse width ranges from 1 - 50 (integer) with a unit of 20ms. The narrowest interval between two pulses is 20ms.In practice th

Seite 110 - Reading

75POWER INSTRUMENTSEvent alarmingWhen the metering data is over the pre-setting limit and over pre-setting time interval, the over limit alarming w

Seite 111

76DPMS XPQ User Manual“Delay time” indicates the time period that the event keeps happening after the setting equation or in equation is satisf

Seite 112

77POWER INSTRUMENTS2. Global settingsThe addresses of all global variables are 101dH~1024H and 103dH in system parameters discussed in c

Seite 113 - Trending Records

6DPMS XPQ User ManualPurposePowerful Multifunction Power MeterThe DPMS XPQ series multifunction power meter is the new generation of the very popular

Seite 114

78DPMS XPQ User Manual“Alarming output to RO2” decides which alarm will be output to RO2. It is set the same as RO1.“Alarming output to DO1 setting”

Seite 115

79POWER INSTRUMENTSno output. The CT primary value of I1 is 200A. The primary voltage of U1 is 10000V, PT2 is 100V. Then let’s look how all the

Seite 116

80DPMS XPQ User ManualFig 4.15 Alarm SettingEvent alarming settingThere are 16 of records to be stored. But they are not corresponding to settin

Seite 117

81POWER INSTRUMENTSaddress parameter range1540H First group: alarming status 0~655361541H First group: parameter number 0~2461542H First group:

Seite 118 - Harmonics:

82DPMS XPQ User ManualFig 4.16 Alarm LogSOE FunctionThere are 4 DI inputs, it can record changing information of DIs. The time resolution is 1ms. It

Seite 119

83POWER INSTRUMENTSon and it works in a cycle. The data won’t lose during power off SOE will set bit0 of “system status” to be 1. At the same time, co

Seite 120

84DPMS XPQ User ManualWaveform recordThe DPMS XPQ can record 5 cycles of waveforms both before and after the trigger point of the entire 6 input cha

Seite 121

85POWER INSTRUMENTSHere is an example:Fig 4.18 Waveform LogTrending recordsThe DPMS XPQ-G takes records of frequency, UA (or UAB), IA, UB (or UB

Seite 122 - MAX/MIN record

86DPMS XPQ User Manualnot be changed. “Trending record backup pointer” is used by the controller, it stores the serial number that the contr

Seite 123

87POWER INSTRUMENTSVoltage EligibilityThe DPMS XPQ-G can take the statistics of voltage eligibility, then give out a great amount of data.Eligibility

Seite 124

7POWER INSTRUMENTSRemote Power ControlThe main function of the DPMS XPQ is measurement, but it also has some exible I/O functions. This makes the me

Seite 125 - Relay Status:

88DPMS XPQ User ManualFig 4.20 Voltage Eligibility Ratio

Seite 126

Chapter 5 CommunicationIntroducing Modbus ProtocolFormat of CommunicationData Address Table Application Details89

Seite 127 - Appendix

90DPMS XPQ User ManualThis chapter mainly discusses how to handle the meter via the communication port using software. To master this

Seite 128 - Current Input

91POWER INSTRUMENTSFraming Address Function Data Check8-Bits 8-Bits N×8-Bits 16-BitsTable5.1 Data Frame FormatAddress FieldThe address field

Seite 129 - Accuracy

92DPMS XPQ User Manualregister addresses, the quantity of items to be handled, and the count of actual data bytes in the eld. For example, if the

Seite 130

93POWER INSTRUMENTSthe CRC. Start and stop bits, and the parity bit, do not apply to the CRC. During generation of the CRC, each 8-bit character is ex

Seite 131

94DPMS XPQ User ManualCRC16 Hi: CRC high byteCRC16 Lo: CRC low byte1. Read Status of Relay (Function Code 01)This function code is used to read status

Seite 132 - DPMS XPQ

95POWER INSTRUMENTS2. Read the Status of DI (Function Code 02)1=On, 0=Off.There are 4 DIs. The Address of each DI is DI1=0000H, DI2=0001H, D

Seite 133

96DPMS XPQ User Manual3. Read Data (Function Code 03)QueryThis function allows the master to obtain the measurement results of the meter.Table 5.

Seite 134 - Experience the Power

97POWER INSTRUMENTSThe example below is a request to meter number 17 to turn on Relay1.Addr Fun DO addr hi DO addr lo Value hi Value lo CRC 16 Hi CR